Here you can define the time settings for the access functions, e.g., the unlocking time, and the functions of the relay outputs and optocoupler inputs of the GC7.3000.

...

Short description of settings

  • Unlocking time: This setting determines the time (in seconds) that the unlocking process is active after a user with a valid access authorization identifies themselves at the reader. If a signal is detected by the feedback contact during the unlocking time, the unlocking process is terminated, and the device returns to its default state.

  • Release device at: Here you configure when the unlocking process is considered to be completed by the GT7 or GC7. This is possible either as soon as the door is opened or the turnstile is turned (start of the feedback signal) or only when the feedback signal is deactivated again or the door is closed.

  • Deny time: This setting determines the time (in seconds) that the denial process is active for after a user with invalid access authorization identifies themselves at the GT7 or GC7.

  • Double door system (timeout): With this locking function, the status of two doors is considered. After passing through the first door, the GT7 or GC7 will continue to block access until the feedback from the second door is deactivated (see optocoupler "Lock feedback"). If the feedback from the second door is not deactivated within the timeout time entered here, the GT7 or GC7 aborts the access process and returns to its default state.

...